TM54120-383-14
4-17.
CONDENSER AIR DISCHARGE LOUVER AND LINKAGE.-Continued
a.
Clean/Inspect.
(1) Disconnect power at power source.
(2) Remove top rear cover (para 4-11).
(3) The louver can be cleaned with a soft brush or washed
with water and a mild detergent solution.
(4) Check louver for bent blades, missing or damaged gaskets,
and missing hardware or bearings.
(5) Clean linkage with a soft brush and damp rag.
(6) Check push-pull cable attaching hardware (mechanical post
and screws etc.) for tightness.
Adjustment.
b.
DANGEROUS CHEMICAL is used in this equipment.
DEATH
or severe injury may result if personnel fail to
observe safety precautions.
Do not attempt to loosen or remove any of the
connections to the copper tubing.
Use great care to avoid contact with liquid
refrigerant or refrigerant gas being discharged under
pressure.
Sudden and irreversible tissue damage can
result from freezing.
(1) If unit has been operating wait until it has cooled to
ambient temperature approximately four hours.
(2) Loosen mechanical post screw on louver connecting link.
(3) Close louvers.
(4) Pull wire tight with needle nose pliers and tighten
mechanical post screw.
(5) Louvers must be tightly closed.
450
|