TM5-4120-383-14
4-17.
CONDENSER AIR DISCHARGE LOUVER AND LINKAGE.-Continued
Replacement.
c.
Do not tamper with cylinder or refrigerant tubing
connections.
If actuating cylinder is suspected bad,
contact direct support maintenance.
(1) Louver blade only.
NOTE
Individual Louver Blades are flexible enough for
removal.
q Remove
top rear cover (para 4-11).
Remove push on nut from louver blade to be removed.
Flex or spring blade to remove ends from bearings.
Remove blade.
Replace bearings if they are damaged.
Flex or spring new blade and install.
Install push on nut.
(2) Louver and linkage assembly removal.
(See para 4-12.)
Remove condenser air inlet guard.
Loosen mechanical post screw and pull push-pull
control cable wire from louver connecting link.
Remove four screws and lock washers and two snap
fasteners.
Slide louver assembly from unit.
Remove push-pull control cable and attaching hardware
(mechanical post, screws, etc.).
Inspect all parts and replace if damaged.
4-51
|