TM5-4120-383-14
4-28.
JUNCTION BOX WIRING HARNESS.-Continued
Disconnect input power from the air conditioner
before performing maintenance on any part of the
electrical system. The voltages used can be lethal.
Inspect.
a.
(1) Disconnect power at power source.
(2) See paragraph 4-21a and remove control module.
(3) Remove top front cover (para 4-11).
(4) Remove seven screws and lock washers and carefully slide
junction box out of unit.
(5) Inspect connector for loose, damaged or missing pins.
Replace if defective.
(6) Check individual wires for loose solder connections,
loose terminal lugs, cut or frayed insulation cut or broken wires.
Tag and disconnect individual wires and connectors
b. Removal.
from unit.
See wiring diagram figure 4-4. Continuity test
Testing.
c.
individual wires. Replace or repair wires with no continuity.
d.
Repair.
(1) See paragraph 4-20 for general wire repair instructions.
(2) See table 4-3 Wire List for wire lengths and terminal
information when individual wires are replaced.
Replace individual wires, terminals
Replace.
e.
or
connectors
if defective.
Installation.
f.
(1) See wiring diagram figure 4-4 and tags and connect the
wire leads and connectors. Remove tags.
(2) Carefully slide junction box into place and secure with
seven screws and lock washers.
4-78
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |