TM5-4120-383-14
MISCELLANEOUS CABLES, HARNESSES, AND TERMINAL BOARDS.-
4-31.
Continued
(2) Remove top rear cover (para 4-11) for access to
compressor and auxiliary power input cables.
(3) For full access to terminal blocks TB2 and TB3 it is
necessary to:
(a) Remove top front cover (para 4-11).
(b) Remove junction box and control module (para 4-21 and
4-27).
(4) Check terminals on terminal boards that they are tight
and free of corrosion.
(5) Disconnect connectors and check for loose, damaged, or
missing pins.
(6) Check individual wires for loose solder connections, cut
or frayed insulation and cut or broken wires.
(7) See wiring diagram (fig. 4-4) and continuity test
individual wires. Repair or replace wires with no continuity.
b. Repair.
(1) See paragraph 4-20 for general wire repair instructions.
(2) See table 4-3 Wire List for wire lengths and terminal
information when individual wires are replaced.
c. Replace.
Replace individual wires, connectors, or terminal
boards if defective.
Installation.
d.
(1) Connect all disconnected connectors.
(2) Install junction box and control module (para 4-21 and
4-27).
(3) Install top front and rear covers (para 4-11).
(4) Connect power at power source.
4-85
|