5-11. DISCHARGING THE REFRIGERANT SYSTEM - Continued
NOTE
In accordance with Environmental Protection Agency regulations refrigerants
cannot be discharged into the atmosphere, A refrigerant recovery & recycling unit
must be used whenever discharging the refrigerant system.
Disconnect power at power source.
a.
b. Remove four screws and refrigerant charging valve access cover.
c. Connect charging manifold to charging valves.
NOTE
Operation of the recovery/recycling unit must be by AUTHORIZED PERSON-
NEL ONLY
d. Connect and operate a recovery/recycling unit in accordance with the manufacturer's instructions.
Discharge the refrigerant system. (See para 5-11.)
Preliminary procedures:
Nitrogen cylinder (item 8, Appendix E)
Supplies: