PURGING THE REFRIGERANT SYSTEM.-Continued
Allow nitrogen to flow through the system at the rate of 1 -
j.
2 cfm (0.028 - 0.057 m3/minute) for a minimum of 5 minutes before
starting any brazing operation, then allow it to continue to flow
at the same rate until all brazing operations are completed.
After installation brazing operations are completed, allow
k.
nitrogen to flow for a minimum of 5 minutes.
Close nitrogen cylinder valve, nitrogen regulator, charging
l.
manifold valve, and both high and low pressure charging valves on
the unit.
Disconnect hose from nitrogen tank.
m.
n.
Assuming that all repairs are completed, go to paragraph
Nitrogen Tank Connection