5-16.
CHARGING THE REFRIGERANT SYSTEM.-Continued
Open the two charging manifold valves.
e.
f.  Open Refrigerant-22 tank valve slightly to allow a small
amount of refrigerant to purge air from hoses.  Tighten hose
connections at the air conditioner charging valves.
g.  Close low pressure (suction) charging manifold valve.  Never
introduce liquid refrigerant into low pressure (suction) charging
valve.
Position Refrigerant-22 tank so that liquid will be used for
charging. (Some drums must be inverted and some are equipped with
a selector valve.)
Use accurate scales to measure and record weight of
i.
Refrigerant-22 drum.
Open Refrigerant-22 drum valve.
j.
k.  Open high pressure charging valve on air conditioner.  Allow
liquid refrigerant to enter system until drum weight has decreased
by 2.2 pounds (1.0 Kg) or until system pressure has equalized.
l.  Close refrigerant drum valve and high pressure (discharge)
manifold valve.
Reset low pressure cut out switch.
m.
Connect power at power source.
n.
o.  Turn air conditioner on and operate in cool mode with
TEMPERATURE SELECTOR set at maximum COOLER position.
If 2.2 pounds (1.0 Kg) full charge was obtained, skip steps
p.
If system pressure equalized prior to obtaining a
q. through s.
full charge of 2.2 pounds (1.0 Kg) proceed with step q.
Switch refrigerant drum to gas only position.
q.
r.  Be sure refrigerant drum has been switched to gas position
and open refrigerant drum valve, low (suction) pressure charging
manifold valve and low (suction) pressure charging valve on air
conditioner.
s.  Monitor weight of the refrigerant drum as air conditioner
compressor pulls additional refrigerant gas into system until full
2.2 pounds (1.0 Kg) charge is obtained.  When system is fully
charged, immediately close refrigerant drum valve and air
conditioner low pressure charging valve.