5-16.
CHARGING THE REFRIGERANT SYSTEM.Continued
Run air conditioner in COOL mode (with temperature control
t.
in coolest position) for 15 minutes.
Do not skip the next step.
u.  After 15 minutes, observe sight glass on back of condenser
Be sure that the refrigeration system is not in bypass.
section.
When system goes into bypass bubbles will appear in the sight
glass.
Green center means refrigerant moisture content is
q
acceptable.
Yellow center means there is too much moisture in system.
q
It must be discharged, evacuated, and charged again.
Milky white or bubbly liquid means system has a low
q
charge.
Clean bubble-free liquid around center means the system is
q
fully charged.
v.
If charge is low add gas refrigerant.
(1) Be sure drum is switched to gas position. Open drum
valve.
(2) Continue to charge until sight glass is clean and bubble-
free.
(3) Close low pressure air conditioner charging valve and
refrigerant drum valve.
w.
Turn MODE SELECTOR switch to OFF.
x.
Check that high and low pressure air conditioner charging
valves are closed and remove charging manifold hoses.
Install charging valve access cover.
y.
5-40