Click here to make tpub.com your Home Page

Page Title: ACTUATING CYLINDER.
Back | Up | Next

Click here for thousands of PDF manuals

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Logistics
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
   
   

 

TM5-4120-383-14
ACTUATING CYLINDER.
The actuating cylinder is located in the rear (compressor/
condenser) compartment.
a.
Removal.
(1) Disconnect power at power source.
(2) Remove top front and rear covers (para 4-11).
(3) Discharge and purge refrigeration system per paragraphs
5-11 and 5-12.
(4) Remove screw from the mechanical post assembly and slip
the push-pull cable wire loose.  Take care not to lose mechanical
post.
(5) Disconnect actuator cylinder from the flare nut on elbow.
(6) Remove two nuts and lock washers and slip actuator
cylinder out of the unit.
b.
Inspect/Replace.
Inspect actuating cylinder for defects and
broken or missing parts.  Replace if defective.
Installation/Adjustment.
c.
(1) Align studs on actuating cylinder with holes in bulkhead
and secure with two each lock washers and nuts.
(2) Connect swivel elbow flare nut to actuating cylinder.
(3) Loose assemble control cable and mechanical post.
(4) Close condenser discharge air louvers.
(5) Pull wire from push-pull cable tight and tighten screw in
mechanical post assembly.
(6) Replace dehydrator. (See para 5-30.)
(7) Leak test newly connected joints and all connections in
the area.
(8) Install top front and rear covers (para 4-11).
(9) Evacuate and charge the refrigeration system in
accordance with paragraphs 5-15 and 5-16.