TM5-4120-383-14
5-26.
PRESSURE
SWITCHES.-Continued
Inspect.
a.
(1) Disconnect power at power source.
(2) Remove control module and junction box (para 4-21 and 4-
It is not necessary to totally remove all wire connections
26).
and capillary line so long as the junction box can be pulled out
enough to gain access to the pressure switches. Support the
junction box so that wires and capillary line are not damaged.
(3) Remove front and rear top covers (para 4-11).
(4) Inspect pressure switches for visible signs of damage.
Test.
b.
(1) Tag and disconnect wires to pressure switches.
(2) Press reset button on the switch. Use a continuity
tester or multimeter to check for continuity between terminals 1
If there is continuity the switch is
and 2 on each switch.
If no continuity is found on either switch, press
properly closed.
If there is
and release the reset button again on that switch.
still no continuity, that switch must be replaced.
c. Removal. Assuming that steps a. (1), (2), and (3) and b.
(1) above have been done proceed as follows.
(1) Discharge and purge refrigeration system per paragraphs
5-11 and 5-12.
(2) If HIGH PRESSURE switch is to be replaced, remove
conditioned air supply louver (para 4-14) for access to mounting
screws.
(3) Disconnect flare nut at end of capillary line from switch
to be replaced.
(4) Remove two screws and lock washers from switch to be
replaced.
(5) Carefully remove switch and capillary line.
5-61
|