5-32.
COMPRESSOR.-Continued
Remove the nitrogen line from the tubing at point 4
and connect it to the valve at point 6.  Release
nitrogen into the system for approximately 5 minutes
or until moisture ceases to be discharged from the
system.
Remove the nitrogen line from the valve at point 6
and connect it to the valve at point 3.  Release
nitrogen into the system for approximately 5 minutes
or until moisture ceases to be discharged from the
system.
Remove the nitrogen line from the valve at point 3.
Close the suction line and discharge line service
valves.
Cap all open tubing until installation of new
components.
Replace dehydrator (para 5-30).
Reconnect plugs P8 and P9 to receptacles J8 and J9
respectively.
c.
Installation.
The compressor is supplied with a complete charge of
oil.  Take care that oil is not lost when handling
and installing compressor.
(1) Install eight rubber mounting washers in mounting
holes of air conditioner housing and compressor mounting feet.
NOTE
If any refrigeration piping was disconnected with the
compressor removal, transfer the piping to the
replacement compressor before installing it in the
air conditioner.
(2) Carefully set compressor down into unit and install four
flat washers and cap screws.
(3) Tip unit up slightly and install four flat washers and
lock nuts from bottom.
(4) Tighten all four sets of mounting hardware.
5-82