TM5-4120-384-14
1-7.
EQUIPMENT
DATA.
AMBIENT OPERATING
TEMPERATURE RANGE
LOW
-50F (-45C)
+125F (+52C)
HIGH
PERFORMANCE
COOLING CAPACITY
18,000 BTU/HR
HEATING CAPACITY
14,300 BTU/HR
Model
Models
POW'ER REQUIRED
F18H-lS
F18H-3S, F18H-3SA
a n d F18H-3SB
VOLTAGE
208
230
PHASE
Single
3
HERTZ
50/60
60
AMPERAGE
16
25
DIMEIOSIONS
Models
Model
F18H-3S, F18H-3SA
F18H-1S
a n d F18H-3SB
WIDTH
30.0
inch (76.2 cm)
3 0 . 0 i n c h (76 .2 cm)
DEPTH
28.0
inch (71.12 cm)
2 8 . 0 i n c h (71 .12 cm)
HEIGHT
20.0
inch (50.8 cm)
2 0 . 0 i n c h (50 .8 cm)
WEIGHT
265
pounds (120.2 kg)
275 pounds ( 1 24.7 kg
REFRIGERANT
TYPE
R-22
CHARGE
3.6 pounds (1.63 kg) Carrier Compressor
2.8 pounds (1.27 kg) Keco Compressor
Section
III
TECHNICAL PRINCIPLES OF OPERATION
1 - 8 . REFRIGERATION CYCLE.
Cooling Cycle.
(See
a.
The COMPRESSOR (1) takes cold, low pressure refrigerant
gas and compresses it to a high temperature, high
This gas flows through the metal tubing to
pressure gas.
the SPLIT CONDENSER COIL (3A) and (3B) and RECEIVER (4).
Change 2
1-9
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |