|
|
TM5-4120-384-14
2-3.
INDICATORS.
(See
The refrigerant sight glass is the only visual indicator
incorporated in the air conditioner.
The refrigerant sight glass
has a small chamber with a glass window through which the
refrigerant condition can be observed.
It is installed in the
liquid refrigerant line downstream from the condenser coil.
Liquid
refrigerant actually flows through the sight glass chamber only
during cooling cycles when the air conditioner is in operation in
The unit must be operated approximately 15 minutes
the COOL mode.
at maximum cooling prior to checking condition of refrigerant at
sight glass.
The sight glass is equipped with a center indicator
that is moisture sensitive. Dry refrigerant is indicated by the color green, which changes
to chartreuse when the moisture content becomes undesirable, and to yellow when the
level becomes unacceptable. Excessive moisture in the refrigerant may damage or possibly
destroy the compressor. If the liquid refrigerant observed in the sight glass has a milky
appearance, or if frequent bubbles appear, the volume of refrigerant is low and the system
should be charged. Moisture or low charge indications should be reported to direct support
maintenance for appropriate refrigeration system action.
Do not operate the air conditioner in the COOL mode
if the refrigerant color has reached the yellow band
or if numerous bubbles appear in the sight glass.
COOL mode operation may be continued with the
refrigerant color in the chartreuse band or with only
an occasional bubble appearing in the window, but the
sight glass should be rechecked after each four hours
of operation to insure that the condition has not become worse. Damage to
the equipment may result if Personnel fail to observe precautions.
Change 1
2-5
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |