TM5-4120-384-14
Table
3-1.
OPERATOR
TROUBLESHOOTING-Continued
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
Step
2.
Check operation of TEMPERATURE SELECTOR.
Set control at maximum COOLER, then, if
condition  improves,  adjust  properly.
Step
3.
Check  that  supply  and
return
air
louvers
are
properly  adjusted.
Adjust
louvers
properly.
Check  that  excessive  hot,  outside  air
is
not
being
Step
4.
introduced  through  fresh  air  damper.
Fully  close  damper,
then,
if
condition
improves,
adjust  properly.
Step
5.
Check  that  all  doors,  windows,  and  other
openings
in  room  or  enclosure  are  tightly  closed.
Tightly
close
all
openings.
Step
6.
Check that condenser air inlet guard or discharge
air  louver  are  not  obstructed.
Remove
obstruction.
Check
condition
of
refrigerant
in
sight
glass.
Step
7.
If  refrigerant  color  is  in  the  yellow  zone  or
numerous  bubbles  appear  in  window,  turn  selector
to  OFF  and  contact  direct  support  maintenance.
3. REDUCED HEATING CAPACITY.
See that MODE SELECTOR switch is properly set.
Step
1.
Set switch on LOW or HIGH HEAT.
Check operation of TEMPERATURE SELECTOR switch.
Step
2.
Set  control  to  fully  WARMER
then,
if
condition
improves,  adjust  properly.
3-3