TM5-4120-38414
Table 41.
ORGANIZATIONAL PREVENTIVE MAINTENANCE
CHECKS AND SERVICES (PMCS)
QUARTERLY SCHEDULE-Continued
Para
Item
Item to be
Ref.
No.
Procedures
Inspected/Serviced
4-12
a.
Remove, clean, inspect, and
10
Air
Inlet
Guard
repair guard, as necessary.
Place guard aside for the
b.
present and reinstall after
item 14.
Compressed air used for
cleaning purposes will
not exceed 30 psi
( 2 . 1 k g / c m2 ) .
4-39
a. Blow accumulated dust and dirt
Coil
out of air passages in con-
denser coil using compressed
air or the discharge side of a
Blow
portable vacuum cleaner.
from inside for reverse
airflow direction.
Inspect coil for obvious
b.
damage and all mounting hard-
ware for tightness and
security.
4-35
a. Wipe or vacuum dust and
12
Condenser Fan and
dirt from fan and motor and
Motor
all other components and sur-
faces in the immediate area.
Inspect fan for damage or bent
b.
blades, motor for signs of
overheating, and all mounting
hardware for tightness and
security.
c.
Inspect wiring harness for
damage or chafing and all
electrical connections for
tightness.
4-25
|