4-8.
USE OF TROUBLESHOOTING TABLE.-Continued
closely  describes  the  immediate  situation;  then  perform  the  test
and  inspections  and  corrective  action  steps  in  the  order  in  which
they  are  listed.
This  manual  cannot  list  all  possible  situations  which  may
c.
be  encountered,  nor  can  it  list  all  test  and  inspection,  and
If  a  condition  is
corrective action steps which may be taken.
encountered  which  cannot  be  resolved  within  the  capabilities  and
experience  of  organizational  maintenance  personnel  assistance
should  be  requested  from  direct  support  maintenance.
TROUBLESHOOTING
Table
4-2.
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
1.
AIR CONDITIONER DOES NOT START IN ANY MODE.
Step
1.
Check
if
circuit
breakers
are
tripped.
Reset
circuit
breakers.
Step
2.
Check
if
input
power
has
been
disconnected.
Connect input power.
Disconnect  input  power  before  performing
Voltages
internal  electrical  troubleshooting.
used  can  be  lethal.
If  input  power  has  been  disconnected  for  an
unknown  period  of  time,  do  not  start  in  COOL
MODE until power has been reconnected for a
minimum  of  four  hours.
Step
3.
Check  for  loose  or  damaged  electrical
connectors
or
damaged  wires  in  wiring  harnesses.
Tighten
or
replace
connectors,
or
repair
damaged
wires.
4-29