TM5-4120-384-14
4-21. CONTROL MODULE. - Continued
(See
Test/Repair.
b.
(1) See paragraphs
through
4-25
for
testing
of
individual components.
(2) Repairs are limited to replacement
of
individual
components and repair of wire connections.
Replace.
If the control module
is
damaged
beyond
repair,
c.
replace with a new control module.
Installation.
(See
d.
(1) Carefully work sensing bulb through junction
box
frame
and
into mounting clamp(s) behind return air louver.
(2)
Tighten
clamp
screw(s).
(3) Slip control module into the opening in junction box.
Take care not to crush or kink sensing bulb capillary line.
(4)
Tighten
control
module
mounting
screw.
(5)
Install
return
air
louver
and
secure
with
eight
screws.
(6)
Connect
power
at
power
source.
4-64
Change 2
|