TM5-4120-384-14
4 - 3 0 . MISCELLANEOUS CABLES, HARNESSES, AND TERMINAL BOARDS.
Disconnect input power from the air conditioner before
performing maintenance on any part of the electrical
system.
The voltages used can be lethal.
Inspect/Test.
a.
(See
(1)
D i s c o n n e c t power
at
power
source.
( 2 ) R e m o v e t o p rear cover on F18H-3S and F18H-1S or top cover
on F18H-3SA and F18H-3SB (para 4-11) for access to compressor and
auxiliary power input cables.
(3) For full
access
to
terminal
blocks
TB2
and
TB3
it
is
necessary to:
(a) Remove top front cover and top center cover on F18H-3S
and F18H-1S or top cover on F18H-3SA and F18H-3SB (para 4-11).
(b)
Remove
junction
box
and
control
module
and
4-26).
(4) Check terminals
on
terminal
boards
that
they
are
tight
and
free of corrosion.
(5) Disconnect
connectors
and
check
for
loose,
damaged,
or
missing pins.
(6) Check individual wires for loose solder
connections,
cut
or
frayed insulation and cut or broken wires.
(7) See wiring diagram (fig. 4-4) and continuity test
individual wires.
Repair or replace wires with no continuity.
b.
Repair.
(1)
See
for
general
wire
repair
instructions.
(2) See table 4-3 Wire List for wire lengths
and
terminal
information when individual wires are replaced.
4-85