TM5-4120-384-14
HARNESSES, AND TERMINAL BOARDS. -
4-30.
MISCELLANEOUS
CABLES,
Continued
c.
Replace.
R e.p l a c e
individual
wires,
connectors,
or
terminal
boards
defctive.
Installation.
d.
(1)
Connect
all
disconnected connectors.
(2)
Install
junction
box
and control
module
and
4-26).
( 3 ) I n s t a l l t o p c e n t e r , front, and rear covers on F18H-3S and
F18H-1S or top cover on F18H-3SA and F18H-3SB (para 4-11).
(4)
Connect
power
at
power
source.
TRANSFORMER, RECTIFIER, CAPACITORS, MD HARNESS.
4-31.
Designation C2
applies to models F18H-3S, F18H-3SA
and F18H-3SB.
This designation changes to C6 on
model F18H-1S.
The transformer, rectifier, and capacitors C1 and C2 are located
behind the junction box in the upper front left corner of the unit.
(See fig. 4-27.)
Disconnect input power from the air conditioner
before performing maintenance on any part of the
The voltages used can be lethal.
electrical system.
a.
Inspect.
(1)
Disconnect
power
at
the
power
source.
(2) (Models F18H-3S and F18H-1S) Remove top front cover
(Models F18H-3SA and F18H-3SB) Remove top cover
(3)
Remove
junction
box
and
control
module
and
4-27).
(4) Check that
connections
and
terminals
are
tight
and
in
good condition.
(5) Check that
harness
wires
have
no
cuts,
broken
wires,
or
frayed insulation.
(6) Check
that
attaching
hardware
is
tight
and
in good
4-87
Change 2
condition.
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |