TM5-4120-384-14
4-32.
EVAPORATOR FAN, MOTOR, AND HOUSING. -Contiued
(16) Carefully
position
sensing
line
and
bulb
in
position
over
left bell inlet.
(17) Secure sensing line and bulb in
position
on
bell
inlet
with loop clamp, screw, and lock washer.
(18)
Connect
P3
and
hand
tighten.
(19) Secure power
cable
to
housing
with
loop
clamp,
screw,
and
self-locking nut.
(20) Install return air
louver
assembly
and
secure
with
eight
screws and lock washers.
(21)
Connect
power
at
power
source.
4 - 3 3 . HEATER THERMOSTAT.
The heater thermostat S6 mounts on the forward inside surface of
the top center cover on models F18H-3S and F18H-1S and on the
evaporator angle on models F18H-3SA and F18H-3SB.
(See fig. 4-29.)
Figure
4-29.
Heater Thermostat
4-96
Change 2
|