4-33.
HEATER
THERMOSTAT.-Continued
(3)  (Models  F18H-3S  and  F18H-1S  only)  Attach
thermostat
and
bracket  to  top  center  cover  with  two  screws.
(4) Install top front cover on F18H-3S and F18H-1S or top
cover on F18H-3SA and F18H-3SB (para 4-11).
(5)
Connect
power
at
power
source.
4-34.
HEATER ELEMENTS.
The  heater  elements  are  located  in  the  upper  front
compartment
behind  the  evaporator  coil.
Disconnect  input  power  from  the  air  conditioner
before  performing  maintenance  on  any  part  of  the
electrical  system.
The  voltages  used  can  be  lethal.
Allow  heaters  to  cool  before  touching.
Severe
burns
can  result  from  touching  hot  heaters.
a.
Inspect/Test.
(1)
Disconnect
power
at
power
source.
(2) (Models F18H-3S and F18H-1S) Remove three top covers
(Models F18H-3SA and F18H-3SB) Remove top cover
(3)  To  gain  access  to  terminal  board  TB2  where  heater  element
leads  are  connected  the  junction  box  and  control  module  must  also
be  removed.
(See  para  4-21  and  4-26.)
(4)  Visually  inspect  each  heater  for  obvious  damage,
deformation,  cracked  or  broken  sheath,  burnt  out  spots,  and
loose,
broken,  or  otherwise  damaged  leads.
(5)
Use  a  multimeter  to  check  continuity
of
each
Continuity  should  be  indicated.
element.
Removal.
b.
(1)
Tag
and
disconnect
leads
from
terminal
board
TB2.