SOLENOID VALVE (COIL REMOVAL).-Continued
(3)  Place  coil
assembly
and
data
plate
on
to
valve
body
and
secure with nut.
(4)
Reconnect
connector
plug.
(5)  Secure  wires  to  existing
harnesses
with
new
plastic
tie
down  straps  or  laacing  cord.
(6)  (Models  F18H-3S  and  F18H-1S)  Install  top  rear  cover  and
(Models F18H-3SA and F18H-3SB) Install
fabric  cover  (para  4-11).
top  cover  and  fabric  cover  (para  4-11).
(7)
Connect
power
at
power
source.
LOW PRESSURE CUTOUT SWITCH (LPCO) JUMPER.
4-38.
If  unit  is  to  be  operated  in  the  "cool"  mode  at  or  below  0F
(-17.8C)  ambiant  the  low  pressure  cutout  (LPCO)  switch  (S5)  must
See  figure  4-34  and  proceed  as  follows:
be jumpered.
Disconnect  input  power  from  the  air  conditioner
before  performing  maintenance  on  any  part  of  the
The  voltages  used  can  be  lethal.
electrical  system.
Disassemble.
a.
(1)
Disconnect
power
at
power
source.
(2)  Remove  control  module  and  junction  box  (para  4-21  and
It  is  not  necessary  to  totally  remove  all  wire  connections
4-26).
and  capillary  line  so  long  as  the  junction  box  can  be  pulled  out
Support  the
enough  to  gain  access  to  the  pressure  switches.
junction  box  so  that  wires  and  capillary  line  are  not  damaged.
(3)  (Models  F18H-3S  and  F18H-1S)  Remove  top  front  cover  (para
4-11).  (Models  F18H-3SA  and  F18H-3SB)  Remove  top  cover  (para  4-11).
(4) Install jumper wire (20 AWG minimum) between terminals
Check  that  jumper  will  not
and  2  of  low  pressure  cutout  switch.
short  out  against  frame  of  control  panel.
4-111