TM5-4120-384-14
SOLENOID VALVE (COIL REMOVAL).-Continued
(3) Place coil
assembly
and
data
plate
on
to
valve
body
and
secure with nut.
(4)
Reconnect
connector
plug.
(5) Secure wires to existing
harnesses
with
new
plastic
tie
down straps or laacing cord.
(6) (Models F18H-3S and F18H-1S) Install top rear cover and
(Models F18H-3SA and F18H-3SB) Install
fabric cover (para 4-11).
top cover and fabric cover (para 4-11).
(7)
Connect
power
at
power
source.
LOW PRESSURE CUTOUT SWITCH (LPCO) JUMPER.
4-38.
If unit is to be operated in the "cool" mode at or below 0F
(-17.8C) ambiant the low pressure cutout (LPCO) switch (S5) must
See figure 4-34 and proceed as follows:
be jumpered.
Disconnect input power from the air conditioner
before performing maintenance on any part of the
The voltages used can be lethal.
electrical system.
Disassemble.
a.
(1)
Disconnect
power
at
power
source.
(2) Remove control module and junction box (para 4-21 and
It is not necessary to totally remove all wire connections
4-26).
and capillary line so long as the junction box can be pulled out
Support the
enough to gain access to the pressure switches.
junction box so that wires and capillary line are not damaged.
(3) (Models F18H-3S and F18H-1S) Remove top front cover (para
4-11). (Models F18H-3SA and F18H-3SB) Remove top cover (para 4-11).
(4) Install jumper wire (20 AWG minimum) between terminals
Check that jumper will not
and 2 of low pressure cutout switch.
short out against frame of control panel.
4-111
Change 2
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |