TM5-4120-384-14
CONDENSER FAN, MOTOR, AND HOUSING REPAIR. - C o n t i n u e d
5-9.
Coat shaft surfaces of rotor with oil (MIL-L-2104,
(h)
Grade 20) and slide bearings on shaft ends.
They
should seat against shoulders at the inner ends of
shaft.
Coat washers and load spring with oil (MIL-L-2104,
(i)
Grade 20) and slide them over end of front shaft with
load spring installed first.
Coat bearing cavity of each end-bracket with oil.
(j)
Slide end-bracket carefully into position over shaft so
that OD of bearing enters ID of bearing cavity in end-
bracket.
Work end-brackets onto shaft until bore fits
Keep match-marks made at time of
over end of stator.
disassembly in alignment.
Place
four
screws
in
each
end-bracket.
(k)
Tap around both end-brackets with a plastic or rawhide
(l)
Tighten in alternating
mallet while tightening screws.
Check
sequence until all screws are equally tightened.
for freedom of rotation by turning motor shaft by hand.
There should be no drag or binding.
End play should be 0.002 -
Check end-play of shaft.
(m)
If end-play is not
0.005 inch (0.051 - 0.127 mm).
within limits, disassemble motor and add or remove
shims to adjust.
b.
Motor Assembly,
Custom
Motor
Design,
Model
700-01-0602.
(See fig. 5-3.)
(1)
To
replace
connector:
Loosen
cable
clamp.
(a)
Tag
and
unsolder
leads.
(b)
Remove
old
connector.
(c)
See wiring diagram figure 4-4 and
tags
and
leads
(d)
Remove tags.
to new connector.
Secure
cable
clamp.
(e)
5-20
|