TM5-4120-384-14
5-27. PRESSURE SWITCHES.-Continued
(8)
Install
junction
box
and
control
module
and
4-26).
(9) Install
conditioned
air
supply
louver
(para
if
it
was
removed.
(10) (Models F18H-3S and F18H-1S) Install top front and rear
(Models F18H-3SA and F18H-3SB) Install top
covers (para 4-11).
cover (para 4-11).
(11) Evacuate and charge the refrigeration
system
in
accordance with paragraphs 5-15 and 5-16.
5-28. SERVICE (CHARGING) VALVES.
The service (charging) valves
are
located
in
the
rear
condenser) compartment.
a.
Removal.
(See
(1)
Disconnect
power
at
power
source.
(2) (Models F18H-3S and F18H-1S) Remove top rear cover (para
(Models F18H-3SA and F18H-3SB) Remove top cover (para
(3) Discharge
and
purge
refrigeration
system
per
5-11 and 5-12.
(4) Remove screw, lock washer,
flat
washer,
and
loop
clamp
from the valve to be replaced.
(5) Disconnect
flare
nut
from
valve
to
be
replaced
and
remove
valve from unit.
Inspect/Replace.
b.
Inspect
service
valves
for
damage
and
replace if suspected bad.
Installation.
c.
(1)
Slip
valve
in
place
and
tighten
flare
nut.
(2)
Secure
with
screw,
lock
washer,
flat
washer,
and
loop
clamp.
(3)
Replace
(See
(4) Leak
test
newly
connected
joints
and
all
connections
in
the
area.
Change 2
5-62
|
Privacy Statement - Press Release - Copyright Information. - Contact Us |