![]() TM 5-4120-386-14
4-24. CONTROL MODULE-Continued.
REMARKS
LOCATION/ITEM
ACTION
replacement
17. Temperature
Remove screw (48), nut (49),
a.
NOTE: Switches
flat washer (50), and spacer
Selector
are not repar-
(52) from capillary clamp (51).
Switch
able and may
b.
Remove clamp (51).
only be replaced.
Remove four screws (58),
c.
four flat washers (60),
and four nuts (59) attaching
switch to back plate (66).
d.
Remove switch (61) from control
module.
Clean contacts. Replace switch
e.
if contacts are damaged.
f.
Replace if failed test.
Replace grommet (6) if damaged.
g.
h.
Reassemble into control module
if passed test.
18. Evaporator
Remove two mounting nuts (14),
a.
Fan Speed
lockwasher (15), and Iockring (16).
Switch
b.
Slide switch (13) out backside
of front panel (47).
c.
Clean contacts. Replace switch
if contacts are damaged.
d.
Replace if failed test.
Reassemble into control
e.
module if passed test.
19. Mode
Remove selector knob (11) by
a.
loosening set screw (12).
Selector
Switch
b.
Remove mounting nut (40) and
lockwasher (41).
c.
Slide switch (39) through
back of front plate (47).
d.
C l e a n contacts. Replace
switch if contacts are
damaged.
Replace if failed test.
e.
f.
Reassemble into control
module if passed test.
4-51
|