TM 5-4120-386-14
This task covers:
c.
a.
Removal
Assembly
b.
Disassembly
d.Installation
INITIAL SETUP
Equipment
Condition
c ondition Description
Para
Evaporator Inlet Louver removed.
Evaporator drain tubing removed.
Control Module removed.
Special ToolS
Materials/Parts
Tool Kit SC 5180-90-CL-N18
Methyl-Ethyl Ketone (MEK)(Item 23, App. D)
Industrial Sealant (Item 28, App. D)
LOCATION/ITEM
ACTION
REMARKS
Disconnect air conditioner power
source before doing maintenance
work on the electrical system.
FRONT OF HOUSING
Removal
1. Evaporator Fan
a.
Unplug the electrical
Assembly
comector from the motor.
Remove the bracket (45) by
b.
removing two screws (43)
and two lockwashers (44).
Loosen clamps holding
c.
temperature selector switch
sensing bulb, move bulb to
clear housing.
d.
Remove four screws (5) and
four lockwashers (6) securing
the fan and motor base to the
resilient mounts (3 and 4).
Lift out fan and motor assembly.
e.
4-73
|