4-34. CONDENSER FAN AND HOUSING AND MOTOR-INSPECT/TEST/REPLACE.
This task covers:
a.  Removal
d. Assembly
b. Inspection
e.  Test
c.  Disassembly
f.
Installation
INITIAL SETUP
Equipment
Condition
Para
Condition Description
Top Covers removed.
Condenser Louver removed.
Special Tools
Tool Kit SC 5180-90-CL-N18
LOCATION/ITEM
ACTION
REMARKS
Disconnect air conditioner power
supply before doing maintenance
work on the electrical system.
TOP OF HOUSING
Removal
a.
Tag, disconnect and put aside
the plugs as necessary.
Remove four screws (1)
b.
and four flat washers (2)
securing motor mounting
plate (24) to housing.
Remove wire ties as required.
c.
d.
Loosen two setscrews (25) and
slide shaft extension (26)
from motor shaft.
Loosen five screws (4) to
e.
loosen fan scroll housing (10).
f.
Remove screws, flatwashers,
and lockwashers from clamps
securing service valves
to scroll housing (10).
4-92