TM 5-4120-386-14
4-34. CONDENSER FAN AND HOUSING AND MOTOR-Continued.
LOCATION/ITEM
ACTION
REMARKS
Take care to avoid damaging con-
denser coil while removing motor
and mounting plate from unit.
h.
Lift out motor (3) and mounting
plate (24), and set aside.
Handle tubing at service valves
and pressure relief valve with
special care to avoid kinking
or creating leaks at brazed
joints.
i.
Bend tubing back at service
valves and at pressure relief
valve with extreme care to
permit scroll to be rotated.
Rotate scroll so that lower
j.
opening is at top.
k.
Ease base flange of scroll
up until it extends slightly
above cabinet housing.
1.
Rotate scroll gently toward
condenser louver opening and
lift carefully from housing.
Inspection
a.
Visually inspect impeller (8),
inlet ring (7), shaft extension (26)
and out of round conditions.
b.
Straighten bent vanes on
impeller (8).
Replace unserviceable impeller
c.
(8).
d.
Straighten bent inlet ring (7)
and scroll (10). Replace if
unserviceable.
e.
Replace damaged shaft extension
(26).
4-94
|