5-22. ACTUATING CYLINDER - Continued.
LOCATION/ITEM
ACTION
REMARKS
Removal-
Remove two nuts (5) and two
C.
flat washers (6) from evaporator
(Continued)
side of partition and remove
actuating cylinder.
Installation
Install actuating cylinder
a.
(4) with studs through open-
ings in partition. Install
two flat washers (6) and two
nuts (5) on studs.
b. Connect the flare nut (2).
c.  Insert wire ends into the
opening in mechanical post
of actuating cylinder.
Adjustment
a.
Extend actuator rod until there
is a 1/4 inch (.635 centimeters)
space between inner edge of
mechanical post bracket and
the face of the cylinder.
Tighten the screw (1) on the
mechanical post.
See
b.
Replace dehydrator.
c.
See
Leak test refrigeration system.
See
d.
Evacuate  refrigeration  system.
See
Charge refrigeration system.
e.
Install Top Rear and Center
See
f.
Covers.
5-75