Page Title: TABLE 4-2. TROUBLESHOOTING
Back | Up | Next

Click here for a printable version

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Combat
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
USMC
   
Products
  Educational CD-ROM's
Printed Manuals
Downloadable Books
   

 

TM5-4120-387-14 TABLE   4-2.   TROUBLESHOOTING MALFUNCT ION TEST OR INSPECTION CORRECTIVE  ACTION 1. AIR CONDITIONER DOES NOT START  IN ANY  MODE. Step 1. Check to see if input power has been disconnected. e phase, 50/60 hertz. Step 3. Check to see if compressor circuit breaker is tripped. Slowly PULL out AND PUSH in reset knob TO RESET Circuit Breaker. Step 4. Check for loose or damaged electrical connectors or damaged wires in wiring  harnesses. (See  para  4-43.) Tighten or replace connectors, or repair damaged wires. Step 5. Check  fuses. (See para 4-33.) Replace bad fuse(s). Step 6. Check operation of the auxiliary switch in circuit breaker (CB) Test (CB1) auxiliary switch. (See para 4-32.) Replace circuit breaker if auxiliary switch is defective. Step 7. Check  operation  of  control  power  transformer  (T)  and  capacitor assembly  (C3). Test transformer and capacitor assembly. (See para 4-30 and 4-31.) Replace transformer or capacitor assembly, if defective. Step 8. Check operation of rectifier (CR). Test rectifier. (See para 4-34.) Replace defective rectifier. Step 9. Check all terminals and internal wiring within junction box for tightness and damage. Tighten terminals,   or repair wiring as necessary. (See para  4-27.) 4-32

Privacy Statement - Press Release - Copyright Information. - Contact Us - Support Integrated Publishing

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business