TM5-4120-387-14 TABLE  4-2.  TROUBLESHOOTING  (Cont.) MALFUNCTION TEST OR INSPECTION CORRECTIVE  ACTION Step 10. Check operation of mode selector switch (S). Test  switch. (See para 4-47.) Replace switch, if defective. Step 11. Check operating of fan toggle switch (S7). Test switch. (See para 4-48.) Replace switch if defective. Step 12. Check that high or low pressure cut-out switches (S6 and S7) are not  open. PUSH and release TO RESET. Step 13. Reset  (PUSH)  PRESSURE  CUT-OUT  switch(es)  and  restart  unit. If unit does not start, notify your supervisor and Direct Support  Maintenance. 2. CONDITIONED  AIR  (EVAPORATOR)  AND  CONDENSER  FANS  BOTH  RUN,  BUT  COMPRESSOR  DOES NOT START AFTER TIME DELAY. Step 1. Check to see if HIGH or LOW PRESSURE CUT-OUT switch has tripped. PUSH and release TO RESET. 4-33