TM5-4120-387-14
TABLE 5-2. NORMAL OPERATING PRESSURES (In Full Cooling DECREASE Mode)
Temperatures
Outdoor Ambient
90°F (32°C) Return
Air to Unit
(Dry Bulb)
80°F (27°C) Return
Air to Unit
(Dry Bulb)
70°F (21°C) Return
Air to Unit
(Dry Bulb)
50°F (1OºC)
52-62
Suction
175-195
Discharge
47-57
Suction
165-185
Discharge
45-55
Suction
140-160
Discharge
Pressure Range (psig)
75°F (24°C)
57-67
Suction
235-255
Discharge
53-63
Suction
215-235
Discharge
45-55
Suction
205-225
Discharge
100°F (38°C)
66-76
Suction
300-320
Discharge
60-70
Suction
290-310
Discharge
49-59
Suction
285-305
Discharge
120°F (49°C)
74-84
Suction
370-390
Discharge
70-80
Suction
360-380
Discharge
57-67
Suction
365-385
Discharge
NOTE:
Wet bulb temperature uncontrolled (dry coil)
Pressure ranges are ±5 (Suction) and ±10 (Discharge) psig about the
tested nominal.
TABLE 5-3. NORMAL OPERATING PRESSURES (In By-Pass Cycle)
Temperatures
Outdoor Ambient
90°F (32°C) Return
Air to Unit
80°F (27°C) Return
Air to Unit
70°F (21°C) Return
Air to Unit
50°F (1O°C)
47-57
Suction
105-125
Discharge
47-57
Suction
105-125
Discharge
47-57
Suction
105-125
Discharge
Pressure Range (psig)
75°F (24°C)
47-57
Suction
147-167
Discharge
47-57
Suction
146-166
Discharge
47-57
Suction
142-162
Discharge
100°F (38°C)
47-57
Suction
208-228
Discharge
47-57
Suction
208-228
Discharge
47-57
Suction
205-225
Discharge
120°F (49°C)
47-57
Suction
284-304
Discharge
47-57
Suction
284-304
Discharge
47-57
Suction
280-300
Discharge
5-26
|