TM5-4120-387-14 5-13.  DESICCANT  REFRIGERANT  DEHYDRATOR  (FILTER  DRIER) Preliminary procedure: Remove junction box. (See para 4-29.) Figure 5-10. Desiccant Refrigerant Dehydrator (Filter Drier) NOTE The  dehydrator  must  be  replaced  each  time  the  refrigeration system has been opened. It should be installed just before unit is leak tested. a. Inspect (1) Check for general condition and signs of leakage. If leakage is suspected, leak test per paragraph 5-9. (2) Check that mounting bracket is secure. b. Remove (1) Discharge the refrigerant system per paragraph 5-6. (2) Using two wrenches, loosen and disconnect flare nuts. (3) Using screwdriver, remove  bracket  mounting  screw  and  lockwasher  from right side of air conditioner. 5-27