5-18. TM5-4120-387-14 (2)  Using charging valve. (3) Using two  wrenches,  loosen  and  disconnect  tubing  flare  nut  from wrench, remove two self-locking nuts on U-bolts. (4) Observe position of valve for proper installation. (5) Remove charging valve. c. Installation (1) Position valve in unit as noted during disassembly. (2) Using two wrenches,    restrain valve body and tighten flare nut. (3) Using two wrenches,    secure valve and cap and chain with two self-locking nuts and U-bolt. (4) Replace the dehydrator. (See para 5-13.) (5) Leak test the newly connected joints and all connections in those areas. (See para 5-9.) (6) Evacuate and charge the system. (See para 5-10 and 5-11.) Follow-on  procedure:  1.  Install  top  panel. (See para 4-23.) 2. Install service valve cover. (See para 4-15.) Preliminary  procedure:  1.  Remove  top  panel.  (See  para  4-23.) 2. Remove junction box. (See para 4-29.) Voltages used can kill. Always disconnect power cord to air conditioner  before  performing  any  internal  maintenance. Shutting unit off at its control panel does not disconnect unit  power. a. Test NOTE The following basic instructions apply to both the equalizing solenoid (L2) and the liquid line solenoid (L1). 5-38

Privacy Statement - Press Release - Copyright Information. - Contact Us - Support Integrated Publishing

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business