4120-01-238-4277">
|
|
TM 5-4120-393-14
Table 4-1. UNIT PREVENTIVE MAINTENANCE CHECKS AND SERVICES (PMCS) QUARTERLY SCHEDULE (cont)
Item
Item To Be
Procedures
No.
Inspected/Serviced
9
Condensate Drip Pan, Drain
Tubes, and Drain Trap
a. Wipe any dust or dirt out of the condensate drip pan.
NOTE
The drain trap is located between junction
box number one and the casing wall. Use
a mirror and flashlight, check waterflow.
Remove junction box number one (para
b. Pour about two cups of clean fresh water into the
condensate drip pan and watch for it to flow through
the drain trap at the bottom end of the drain tube.
c. If the water does not flow through the trap, or if the
discharged water has a muddy appearance, remove
the cotter pin, spring, and ball from the bottom end of
the drain tube and thoroughly flush the tube. If the
tube is clogged, insert a flexible wire from either the
top or bottom end and agitate until the clog is
removed. Pour additional water in the drip pan until an
unrestricted flow of clean water is achieved. Check
that ball and sprin g are clean and in good condition.
Reinstall the ball, spring, and cotter pin.
4-28
|