4120-01-238-4277">
|
|
TM 5-4120-393-14
Table 4-1. UNIT PREVENTIVE MAINTENANCE CHECKS AND SERVICES (PMCS) QUARTERLY SCHEDULE (cont)
Item
Item To Be
Procedures
No.
Inspected/Serviced
b. Inspect heating elements and thermostat for obvious
damage, and all mounting hardware for tightness and
security.
c. Inspect wiring harness for damage or chafing and all
electrical connections for tightness.
6
Evaporator Fans and Motors
a. Wipe or vacuum all dust or dirt from the fans, motors,
and all other components and surfaces in the area.
b. Inspect the fans for damage or bent blades, motors for
signs of overheating, and all mounting hardware for
tightness and security.
c. Check that fans spin freely.
d. Inspect wiring harness for damage or chafing and all
electrical connections for tightness.
e. Generally inspect refrigeration system components in
the upper sec tion for condition.
7
Conditioned Air Intake Grille
a. Check operation of louvers for stiffness or binding.
b. Remove, clean, repair, and lubricate grille as
necessary.
8
Lower Front Panel
a. Be sure input power has been turned off, then
disconnect the input power connector if the optional
front panel input location has been used.
b. Remove, clean, and inspect the front panel.
4-27
|