4-58. Heater Elements (HR1 thru HR6)
This task covers:
a. Removal
c. Installation
b. Inspection/Testing
Initial setup.
Tools:
Tool kit, service, refrigeration unit NSN 5180-00-596-1474
Multimeter NSN 6625-00-553-0142
Personnel: 1
Equipment condition:
1.  Turn unit power off at power source. If there is a chance that it will be turned on, also disconnect power cable
to air conditioner.
2.  Remove mist eliminator. See para 4-32.
General Safety Instructions:
WARNING
Disconnect input power to the air conditioner before performing any internal
maintenance. Voltages used can KILL. Shutting the unit off at the control panel
does not disconnect unit power.
REMOVAL
1.
Tag and disconnect the leads from the heater that is being removed.
2.
Using screwdriver, loosen the two captive fasteners in the retainer channel (1).
3.
Pull heater element (2) free of lower mounting clip (3) and remove heating element.
4-133

Privacy Statement - Press Release - Copyright Information. - Contact Us