TM 5-4120-393-14
4-64. Condensate Trap and Drain Tubes
This task covers:
a. Removal
c; Cleaning
b. Inspection
d. Installation
Initial setup.
Tools:
Tool kit, service, refrigeration unit NSN 5180-00-596-1474
Personnel: 1
Material:
Rags, (Appendix E, item 9)
Equipment condition:
1. Turn unit power off at power source. If there is a chance that It will be turned on, also disconnect power cable
to air conditioner.
2. Remove junction box number one. See para 4-40.
3. Remove mist eliminator. See para 4-32.
General Safety Instructions:
WARNING
Disconnect input power to the air conditioner before performing any internal
maintenance. Voltages used can KILL. Shutting the unit off at the control panel
does not disconnect unit power.
REMOVAL
1.
Using pliers, remove cotter pin (1).
2.
Remove spring (2) and ball.
INSPECTION
1.
Check ball, spring,} and cotter pin for nicks and wear.
2.
Replace ball if it is nicked or has any damage that would keep it from sealing properly.
3.
Replace spring if it is worn or has any damage that would keep it from applying pressure to ball.