4120-01-238-4277">
|
|
TM 5-4120-393-14
4-63. Condenser Coil Cleaning (cont)
CLEANING
WARNING
2
Compressed air used for cleaning purposes will not exceed 30 psi (2.1 kg/cm ).
Do not direct compressed air against the skin. Use goggles or full face shield.
CAUTION
Do not use steam to clean coil.
Clean coil (1) with a soft bristle brush, vacuum cleaner and brush attachment, or use compressed air at 30 psi or less from
the inside of the unit to blow the dirt out. Take care to avoid fin damage. When using compressed air, wear safety
glasses or goggles. Dirt can be blown into your eyes. Clean if dirt is evident.
NOTE
FOLLOW ON MAINTENANCE:
1.
Install condenser coil guard. See para 4-28.
2.
Install lower front panel. See para 4-24.
3.
Connect power.
4-145
|