4120-01-238-4277">

 

Click here to make tpub.com your Home Page

Page Title: DISASSEMBLY (cont)
Back | Up | Next

Click here for thousands of PDF manuals

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Logistics
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
   
   

 

TM 5-4120-393-14
5-8. Refrigeration System, General Repairs
WARNING
DANGEROUS CHEMICAL (R22) is used in this equipment.
DEATH
or severe damage may result if personnel fail to observe safety precautions. Use
great care to avoid contact with liquid refrigerant or refrigerant gas being
discharged under pressure.  Sudden and irreversible tissue damage can result
from freezing. Wear thermal protective gloves and a face protector or goggles in
any situation where skin-eye-contact is possible. Prevent contact of refrigerant
gas with flame or hot surfaces. Heat causes the refrigerant to break down and
form carbonyl chloride (phosgene), a highly poisonous and corrosive gas.
REFRIGERANT UNDER PRESSURE
is used in the operation of this equipment.
DEATH
or severe injury may result if you fail to observe safety precautions. Never use a
heating torch on any part that contains refrigerant - 22. Do not let liquid refrigerant
touch you, and do not inhale refrigerant gas.
NOTE
The refrigeration system must be totally discharged before any maintenance action
that requires opening of the pressurized system.  Leak testing and dehydrator
replacement are required after any system component has been removed and
replaced. The system must be evacuated before it is charged. The system must
be properly charged to function properly.
5-16

Privacy Statement - Press Release - Copyright Information. - Contact Us

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business