5-9. Discharging Refrigeration System
This task covers
a. Service
Initial setup
Tools:
Tool kit, service, refrigeration, unit NSN 5180-00-596-1474
Bucket NSN 7240-00-137-1609
Rubber gloves NSN 8415-00-266-8677
Safety goggles NSN 4240-00-052-3776
Recovery and recycling unit, refrigerant NSN 4130-01-338-2707
Personnel: 1
General Safety Instructions-
WARNING
Death or serious injury may result if personnel fail to observe safety precautions.
Use great care to avoid contact with liquid refrigerant or refrigerant gas being
discharged under pressure. Sudden and irreversible tissue damage can result
from freezing. Wear thermal protective gloves and a face protector or goggles in
any situation where skin-eye-contact is possible.
Prevent contact of refrigerant gas with flame or hot surfaces. Heat causes the
refrigerant to break down and form carbonyl chloride (phosgene), a highly
poisonous and corrosive gas.
SERVICE
1.
Remove valve stem protective caps. Take care that they are not lost.
2.
Unscrew hose connection protective caps
3.
Connect the charging manifold hoses to the manifold and air conditioner service valves
4.
Attach a hose assembly to the center connection of the manifold.
Change 2 5-17
|