5-27. Low (S6) and High (S5) Pressure Cutout Switches (cont)
6.
Using wrench, connect flare nut (6).
7.
Using screwdriver, attach capillary line to fan housing with clamp, washer, and screw.
8.
Carefully coil excess capillary tubing and tape in place to eliminate vibration.
9.
Replace dehydrator. See para 5-16.
10. Leak test all newly connected joints and those in the repaired area. See para 5-12.
11. Using screwdriver, secure switch assembly enclosure to unit with four screws (1) and washers (2).
12. Connect P16 connector to J16 connector on enclosure. See para 5-13 and 5-14.
13. Evacuate and charge refrigerant system.
14. Connect power.
15. Press and release pressure switch reset buttons to be sure that they are not tripped.
NOTE
FOLLOW ON MAINTENANCE:
1.
Install lower front panel. See para 4-24.
2.
Connect power.