4120-01-238-4277">
|
|
TM 5-4120-393-14
5-28. Compressor (B1) (cont)
5.
Using screwdriver, loosen screw (5) in heater band clamp (6).
6.
Remove band clamp (6) and two heater halves (7).
7.
Install new heater as follows:
a.
Position heater halves (7) and heater band clamp (6) on compressor.
b.
Using screwdriver, tighten screw (5) in band clamp.
c.
See tags and wiring diagram (para 4-13) and connect wire leads (3) and jumpers (4).
d.
Remove tags.
e.
Using screwdriver, secure the two terminal covers (2) with four screws.
REPLACE THERMOSTAT S10
NOTE
Refrigerant system discharge is not required.
1.
Check to see that the power has been disconnected at the power source and covers have been removed during
access and testing.
2.
Tag and disconnect three thermostat leads at splices (1).
3.
Using screwdriver, remove two screws (2) and nuts (3) that secure support (4) to angle (5).
4.
Remove support (4) and thermostat (6).
5.
Install new thermostat as follows:
a.
Using screwdriver, install support (4) and thermostat (6) with two screws (2) and nuts (3). Be sure thermostat (6)
face is making good contact with side of compressor.
b.
See tags on old thermostat and wiring diagram, para 4-13, install new splices and connect leads.
5-71
|