TM 5-4120-393-14
5-29. Tubing and Fittings
This task covers:
a. Removal
b. Installation
Initial setup.
Tools:
Tool kit, service, refrig eration unit NSN 5180-00-596-1474
Leak detector NSN 4940-00-531-0362
Personnel: 1
Materials:
Rags (Appendix E, item 9)
Equipment condition:
1. Turn unit power off at power source. If there is a chance that it will be turned on, also disconnect power cable
to air conditioner.
General Safety Instructions:
WARNING
Disconnect input power to the air conditioner before performing any internal
maintenance. Voltages used can KILL. Shutting the unit off at the control panel
does not disconnect unit power.
NOTE
The refrigeration system contains a number of pieces of copper tubing in a variety
of material grades, sizes, lengths, and shapes, and a number of elbows, tees, and
adapters in several sizes. Observe the following when replacing any piece of
tubing or fitting in the system.
Remove covers and panels as necessary to have access to repair area.
REMOVAL
1.
Discharge the refrigeration system. See para 5-9.
2.
Purge the system with nitrogen (para 5-10) and debraze (para 5-11) the tube connections.
3.
Remove the part.
5-76
|