REFRIGERATED CONTAINER SYSTEM
SERVICE UPON RECEIPT Continued
0017 00
GENERATOR SET PREPARATION Continued.
7.
Connect five-foot power cable (1, Figure 3) to generator set (2) as follows:
a.
Open terminal box cover (3).
b.
Insert the power cable (1) through the weather boot (4) into the terminal compartment.
c.
Remove fastener tool (5).
d.
Raise retention clips (6) from each terminal.
e.
Connect black wire to terminal L1 (7).
f.
Connect white wire to terminal L 2 (8).
g.
Connect red wire to terminal L3 (9).
h.
Connect green wire to terminal L0 (10).
i.
Use tool (5) to tighten nut (11) on each terminal.
j.
Lower retention clip (6) over each terminal and return tool to storage position.
k.
Close terminal box door (3).