Order this information in Print

Order this information on CD-ROM

Download in PDF Format

     

Click here to make tpub.com your Home Page

Page Title: b. Removal.
Back | Up | Next

Click here for a printable version

Google


Web
www.tpub.com

Home


   
Information Categories
.... Administration
Advancement
Aerographer
Automotive
Aviation
Combat
Construction
Diving
Draftsman
Engineering
Electronics
Food and Cooking
Math
Medical
Music
Nuclear Fundamentals
Photography
Religion
USMC
   
Products
  Educational CD-ROM's
Printed Manuals
Downloadable Books
   

 

TM 9-4110-257-14 4-29. REMOTE BULB THERMOSTAT S2 TESTING AND REPLACEMENT. - Continued (9)   Install clamps (11) and (14), bolt (10), sensing bulb bracket (8), and new self locking nut (9). (10) Install sensing bulb bracket (8), two bolts (7), and new self locking nuts (6). (11) Install cover (5) and screw (4). (12) Close control panel (3) and install two new lock washers (2) and bolts (1). b. Removal. (1)   Be sure battery has been disconnected and remove two bolts (1) and lock washers (2). Open control panel (3).  Discard lock washers. (2)   Remove screw (4) and cover (5). (3)   Remove two self locking nuts (6), bolts (7), and sensing bulb bracket (8). Discard self locking nuts. (4)   Remove self locking nut (9), bolt (10), and sensing bulb bracket (8). Discard self locking nut. (5)   Remove clamp (11). (6)   Tag wire leads (15) then remove two screws (16) and wire leads. (7)   Pull wire leads (15) from remote bulb thermostat (13) and remove grommet (17). (8)   Remove tie down straps (18). (9)   Remove four self locking nuts (19), bolts (20), and flat washers (21). Discard self locking nuts. (10) Remove remote bulb thermostat (13), grommets (22) and (23), and sensing bulb (12). (11) If temperature control switch bracket (24) is damaged, remove two self locking nuts (25), flat washers  (26), screws (27), and bracket.  Discard self locking nuts. (12) If dummy stowage connector (28) or cover (29) are damaged, remove four self locking nuts (30), bolts (31), cover, and dummy stowage connector.  Discard self locking nuts. (13) Remove any silicone RTV remaining in evaporator frame grommets (22). 4-74

Privacy Statement - Press Release - Copyright Information. - Contact Us - Support Integrated Publishing

Integrated Publishing, Inc. - A (SDVOSB) Service Disabled Veteran Owned Small Business