TM 9-4110-257-14 5-20. PRESSURE REGULATOR VALVE (DISCHARGE) REPLACEMENT. - Continued b.  Installation. (1)   Install clamp (5) onto pressure regulator valve (2) and aline clamp.  Install bolt (4) and new self locking nut (3). (2)   Purge (para. 5-8) and braze (para. 5-9) two fittings (1) onto pressure regulator valve (2). NOTE FOLLOW-ON MAINTENANCE: Close left side condenser door. Replace dehydrator (para. 5-14). Leak check (para. 5-10), evacuate (para. 5-11), and charge (para. 5-12) the refrigeration system. 5-44