TM 9-4110-257-14
5-20.
PRESSURE REGULATOR VALVE (DISCHARGE) REPLACEMENT. - Continued
b. Installation.
(1) Install clamp (5) onto pressure regulator valve (2) and aline clamp. Install bolt (4) and new self locking nut (3).
(2) Purge (para. 5-8) and braze (para. 5-9) two fittings (1) onto pressure regulator valve (2).
NOTE
FOLLOW-ON MAINTENANCE:
Close left side condenser door.
Replace dehydrator (para. 5-14).
Leak check (para. 5-10), evacuate (para. 5-11), and charge (para. 5-12) the refrigeration system.
5-44
|