TM 9-4110-257-14
5-21.
PRESSURE REGULATOR VALVE (CRANKCASE) REPLACEMENT. - Continued
b.
Installation.
(1) Purge (para. 5-8) and braze (para. 5-9) two fittings (2) onto pressure regulator valve (3).
(2) Install insulation (1) and wrap with insulation tape.
NOTE
FOLLOW-ON MAINTENANCE:
Close right side condenser door.
Replace dehydrator (para. 5-14).
Leak check (para. 5-10), evacuate (para. 5-11), and charge (para. 5-12) the refrigeration system.
5-46
|