TM 9-4110-257-14
Table 2-1. Operator Preventive Maintenance Checks and Services for Model F10000RD
NOTE
If the equipment must be kept in continuous operation, do only the
procedures that can be done without disturbing operation. Make complete
checks and services when the equipment is shut down.
Location
Item
Item to
Not Fully Mission
No.
Interval
Check/
Procedure
Capable if:
Service
Refrigeration
Unit Exterior
1
Before
Temperature
a.
Temperature gage should indicate
Temperature gage does
Gage
refrigerator enclosure temperature. If it
not indicate refrigerator
does not, notify unit maintenance to
enclosure temperature.
replace it.
b.
Inspect the Temperature gage for cracked
or missing lens and loose or missing
mounting hardware. If damaged or loose,
notify until maintenance to tighten or
replace it as necessary.
Refrigeration
Unit Interior
WARNING
Exposed rotating parts are contained in
the refrigeration unit. Care must be
taken when doors are open to prevent
personal injury.
2
Before
Sight
a.
Inspect sight indicator port for cracks and
Sight indicator port is
Indicator
note center indicator color. If cracked or
cracked or center
yellow, notify direct support maintenance to
indicator color is yellow.
replace it or evacuate the refrigeration
system as necessary.
b.
Inspect the sight indicator for evidence of
Evidence of leak is
refrigerant leak. If evidence of leaking
found.
found, notify direct support maintenance to
replace it.
2-10
|