TM 9-4110-257-14
Table 2-1. Operator Preventive Maintenance Checks and Services for Model F10000RD-Continued
Location
Item
Item to
Not Fully Mission
No.
Interval
Check/
Procedure
Capable if:
Service
Refrigeration
Unit Exterior
NOTE
The gages must not be inspected when
the DEFROST IN PROGRESS lamp is
on.
Pressures given are the acceptable
operating range.
13
During
Pressure and
Inspect the pressure gage for reading between
Gage reading above or
Compound
160 and 270 psi (1104 and 1863 kPa) and the
below acceptable
Gages
compound gage for reading between 0 and 15 psi
operating range.
(0 and 104 kPa). If either gage is out of
acceptable operating range on a continuous basis,
note the readings and shut down the
refrigeration unit (para 2-7). Notify unit
maintenance of the pressure readings.
NOTE
The temperature gage must not be
inspected when the DEFROST IN
PROGRESS lamp is on.
14
During
Temperature
Temperature gage should indicate within 15 F
Temperature gage
Gage
(8 C ) of remote bulb thermostat setting. If out
indicates more than 15°
of this range, shut down refrigeration unit
F (8° C) above or below
(para 2-7) and notify unit maintenance.
remote bulb thermostat
setting.
2-13
|